Conow Local for Home Assistant

Conow Local

A local Modbus RTU/TCP integration that connects CONOW balcony-solar storage devices to Home Assistant.

Version comparison: v1 and v2

Integration 2.5.0. The v2 register map was finalized on November 4, 2026; v1.0 was released on July 16, 2026.

Both register maps share a single parser and entity model; only the data differs. For each entry, exactly one map is loaded and polled.

Aspect v1 v2
Released Jul 16, 2026 Nov 4, 2026
Register map maps/registers.json maps/panel_registers.json
Selected when the probe of 0x274E fails 0x274E answers (any value)
Polling 5 s per block 30 s per block
Control location HA device-page entities the grouped panel
Write shape one value; the device page refuses and links to the panel whole group, validated, one atomic FC 0x10 frame
After a write waits for the next poll re-read immediately
“Device-page controls are visible but do not write directly … All writes go through that panel, which sends a whole group at once.” v2 grouped panel — Writes

Sources

Protocol documentation and the project repository.

How to use the panel

The procedure covers the complete workflow from device preparation to a confirmed write; demonstration cards play automatically.

1

Prepare the device in the Conow app

In the CONOW app, navigate to Devices → target device → Modbus Service. Enable Modbus TCP or Modbus RTU according to the connection in use, and verify Slave ID 0xA0 and port 502. Dynamic Auth Code must display “Verified”; select Refresh if it does not.

Conow app → Modbus Service (RTU has priority; TCP shows the verification state).

2

Add the integration in Home Assistant

Navigate to Settings → Devices & services → Add integration → Conow Local, and select the connection type that matches the hardware. The form below lists the corresponding fields and default values. After submission, the entry appears under Devices & services; if the attempt fails, refer to the Errors tab.

× Connection type

Select how the device is reached: RS-485 serial, Modbus TCP through an RS-485/Ethernet adapter, or Modbus TCP directly to the all-in-one machine.

CONOW Energy
/dev/ttyUSB0
38400
192.168.1.50
502
160
A1B2C3D4
Submit

The fields correspond to the Home Assistant dialog; default values are pre-filled.

3

Open the panel

The panel is accessible from the sidebar or directly via its URL. It loads the map version reported by the active device.

Panel URL: /conow-local-panel?device_id=… — also available from the Home Assistant sidebar.

Interactive demonstration

The following demonstration cards play automatically and also support manual interaction. Select Replay to restart a card.

Auto

4 Live readings

The panel reads every block of the active map and refreshes the values in place at the polling interval; the layout remains stable.

Conow Local Poll 30 s ↻ Refresh
▾

Real-time Monitoring

Battery Power-820 W
Grid Active Power1,240 W
PV Total Power2,060 W
System SoC64 %
Auto

5 Group editing and submission

After the direction and target power are modified, the values are validated against the device's live limits, contiguous registers are merged, the group is written in a single FC 0x10 frame, and the state is read back immediately.

Conow Local Poll 30 s
▾

Real-time Control

Charge/discharge direction
Target charge/discharge power
320 W
Charge/discharge cutoff SoC
20 %
Charge/discharge duration 120 min
Auto

6 Value range enforcement

Writable registers observe the ranges documented for the device, such as 30–720 min for the control duration. Input outside the permitted range is limited to the nearest boundary and reported.

Conow Local Poll 30 s
▾

Real-time Control

Charge/discharge duration 120 min
Allowed range 30–720 min

7 Write sequence

Every submission follows the same sequence.

1

Validate

Each writable register is validated against its live limits and dependencies.

2

Merge

Contiguous registers are merged into a single atomic FC 0x10 frame; groups with gaps fall back to consecutive FC 0x06 writes.

3

Read back

The device state is read back immediately; the panel does not wait for the next polling cycle.

FC 0x10 Slave 0xA0 Registers 10100–10107 → one frame → read back

Prerequisites

Prerequisites for a working panel.

✓Turn on “Enable External Control / ModBus RTU” in the Conow app (RTU and adapter links).
✓Direct TCP needs the 8-character hex verification code shown by the machine.
✓Slave 160 (0xA0); RTU serial 38400 8N1; TCP port 502.
✓Only one client may hold the device at a time.
✓Reload the integration after changing connection settings.
✓The panel is in the sidebar and at /conow-local-panel.

Error scenarios and messages

The integration reports the specific cause rather than a generic failure. The following messages correspond to the user interface.

Live preview
EX 4 Another client holds the device

The device is already connected by another client (MAC address changed); Modbus I/O has stopped. Close the other connection (Conow app, RS-485 adapter or another Home Assistant instance), then reload the integration or restart Home Assistant.

EX 4

Another client holds the device

The device is already connected by another client (MAC address changed); Modbus I/O has stopped. Close the other connection (Conow app, RS-485 adapter or another Home Assistant instance), then reload the integration or restart Home Assistant.

EX 5

The verification code is stale

The device asks for a manual refresh: the verification code is no longer valid and Modbus I/O has stopped. Update it in Settings → Devices & services → Conow Local → Configure.

EX 6

RTU external control is off

The device's RTU external-control switch is off. Open the Conow app, go to the device panel and turn on “Enable External Control / ModBus RTU”, then reload the integration; polling has stopped.

The device refused the write

{group}: the device refused the write ({error}). Check the values and try again.

No data could be read

No data could be read from the device. Check that it is online and that the serial or network connection is working.

Firmware below v2

Device firmware {firmware} is below {minimum}, which is required for the finalized register map (panel_registers.json); entities are read from registers.json (v1) and the grouped panel is unavailable.

When adding or reconfiguring

Messages displayed in the Home Assistant dialog.

Cannot connectUnable to connect over Modbus. Check the connection, Enable External Control / ModBus RTU, and slave address.
Invalid verification codeVerification code must be exactly 8 hexadecimal characters.
TCP connection failedCannot open a TCP connection. Check that the IP address is correct, the TCP port is open, and Home Assistant is on the same network as the device.
Verification failedThe device rejected the verification code. Check the 8-character code shown on the machine and try again.
Device busyThe device is already connected by another client (MAC address changed). Close the other connection (Conow app, RS-485 adapter or another Home Assistant instance) and try again.
Verification requiredThe device asks for a manual refresh: the verification code is no longer valid. Read the current 8-character code from the machine, then update it under Configure.
External control disabledThe device's RTU external-control switch is off. Turn on “Enable External Control / ModBus RTU” in the device panel of the Conow app, then try again.

Input validation before submission

Displayed below the group while a value is invalid; no data is sent.

rangeOutside the allowed range, adjust: {codes}
emptyFill in every writable field
sameNo changes
timeInvalid time readings, set them again: {codes}
orderInvalid time slots (start before end, no overlaps): {slots}
clamp{name} limited to {value} ({min}–{max})

Values in braces are substituted at runtime.